刘武忠, 林永昕, 李克勇, 赵乾魁, 孙原. 室内空调使用不当致2例急性CO中毒事故报告J. 职业卫生与应急救援, 2018, 36(3): 272-272, 278. DOI: 10.16369/j.oher.issn.1007-1326.2018.03.029
引用本文: 刘武忠, 林永昕, 李克勇, 赵乾魁, 孙原. 室内空调使用不当致2例急性CO中毒事故报告J. 职业卫生与应急救援, 2018, 36(3): 272-272, 278. DOI: 10.16369/j.oher.issn.1007-1326.2018.03.029
LIU Wuzhong, LIN Yongxin, LI Keyong, ZHAO Qiankui, SUN Yuan. Report on two cases of CO poisoning by misuse of indoor air conditionerJ. Occupational Health and Emergency Rescue, 2018, 36(3): 272-272, 278. DOI: 10.16369/j.oher.issn.1007-1326.2018.03.029
Citation: LIU Wuzhong, LIN Yongxin, LI Keyong, ZHAO Qiankui, SUN Yuan. Report on two cases of CO poisoning by misuse of indoor air conditionerJ. Occupational Health and Emergency Rescue, 2018, 36(3): 272-272, 278. DOI: 10.16369/j.oher.issn.1007-1326.2018.03.029

室内空调使用不当致2例急性CO中毒事故报告

Report on two cases of CO poisoning by misuse of indoor air conditioner

  • 摘要: 通过调查发生在某公司司机休息室的一起一氧化碳(CO)中毒事故, 发现中毒原因是废气管道布局设计不合理, 直燃型空调锅炉节气阀垫片损坏没有及时更换垫片, 单靠调节流量泵调节燃气流量, 造成燃气、空气比例失调, 导致大量CO产生, 沿废气管道裂缝进入休息室引起CO中毒。有毒气体管道布局设计时要严格遵守相关规定, 维修作业时应严格管理。

     

/